Our enterprise since its inception, usually regards product top quality as business life, repeatedly enhance manufacturing technology, make improvements to product excellent and continuously strengthen enterprise total high quality administration, in strict accordance with all the national standard ISO 9001:2000 for Automatic Power Factor Controller, Hybrid Power Filter, Capacitor Bank Contactor, Welcome your enquiry, greatest service is going to be provided with full heart.
China Wholesale Series Reactor Quotes - Three phase series filter reactor – LASTONE Detail:
Overview
CKSG series three phase series filter reactors are often affected by harmonic current, switching inrush current and operating overvoltage when compensating capacitive reactive power, which will cause capacitor damage and power factor reduction. Install three phase filter reactors to suppress and absorb harmonics, protect capacitors, avoid the effects of harmonic voltage current and impulse voltage current, improve power quality, increase system power factor, and extend capacitor life
Standard:
● GB/T 1094.6-2011
● GB/T 19212.1-2016
Features
● Designed with secondary thermal sensitive temperature protection switch
● Full vacuum dipping process, low noise during operation
● Winding frame is reinforced environmental protection flame retardant plastic
Model and Meaning
CKSG |
-
|
-
|
-7%
|
P |
K |
│ |
│ |
│ |
│ |
│ |
│ |
1 |
2 |
3 |
4 |
5 |
6 |
No. |
Name |
Meaning |
1 |
Series code |
Dry air-cooled three phase series filter reactor CKDG: single phase |
2 |
Matching Capacitor rated voltage (kV) |
|
3 |
Rated capacity of matched capacitor (kvar) |
|
4 |
Rated reactance rate XL / Xc (%) |
△ :three phase compensation; Y:split phase compensation |
5 |
P: terminal block |
RS485 |
6 |
K: with temperature protection switch |
No mark: without temperature protection switch |
Technical Parameters
Normal working and installation conditions
Ambient temperature |
-25°C~+50°C |
Relative humidity |
Relative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C |
Altitude |
≤ 1000m |
Performance |
|
Rated voltage of capacitor |
0.4 kV、0.45 kV、0.48 kV、0.525 kV、0.66kV、0.69 kV; |
Reactance ratio |
Reactance rate 4.5%, 5%, 6%, 7% is used to limit switching inrush current and suppress 5th and above harmonics
|
Reactance ratio |
Reactance rate 12%, 14%, used to limit closing switching current and suppress 3rd and above harmonics
|
Withstand voltage level 3.5kV / min |
5kV/min |
Insulation class |
B, F, H; Noise ≤ 45dBz continuous operation under overload capacity ≤ 1.35ln |
Dimension and structure |
Product category |
Specification |
Dimension WxDx H(mm) |
Mounting dimensiWxD(mm) |
|
CKSG 7% copper wire |
5~10 kvar |
210x145x170 |
110×85
|
15-25 kvar |
210x155x175 |
110×85
|
30-50 kvar |
240x160x215 |
135×110
|
CKSG 7% Aluminum wire |
5~8 kvar |
210x150x170 |
110×85
|
10-15 kvar
|
210x150x170 |
110×85
|
20-25 kvar
|
240x155x195 |
135×110
|
30-35 kvar
|
240x155x215 |
135×110
|
40-50 kvar
|
262x180x215 |
150×110
|
CKSG 14% copper wire |
25-30 kvar
|
240x160x200 |
135×110
|
CKSG 14% Aluminum wire |
25-30 kvar
|
270x190x215 |
150×120
|
CKSG 14% copper wire. Aluminum wire |
40-50 kvar
|
290x190x240 |
180×120
|
Product detail pictures:
Related Product Guide:
We have been ready to share our knowledge of advertising and marketing worldwide and recommend you suitable products and solutions at most competitive price ranges. So Profi Tools supply you best benefit of money and we're ready to create with each other with China Wholesale Series Reactor Quotes - Three phase series filter reactor – LASTONE , The product will supply to all over the world, such as: Cambodia, New York, Bahamas, Ensuring high product quality by choosing the best suppliers, now we have also implemented complete quality control processes throughout our sourcing procedures. Meanwhile, our access to a large range of factories, coupled with our excellent management, also ensures that we can quickly fill your requirements at the best prices, regardless the order size.