With this motto in mind, we've got become among essentially the most technologically innovative, cost-efficient, and price-competitive manufacturers for Ac Compressor Capacitor, Capacitor For Water Pump Motor, Cbb60 Capacitor, With a wide range, good quality, reasonable prices and stylish designs, our products are extensively used in this industries and other industries.
China Wholesale Reactive Power Compensation Pricelist - Three phase series filter reactor – LASTONE Detail:
Overview
CKSG series three phase series filter reactors are often affected by harmonic current, switching inrush current and operating overvoltage when compensating capacitive reactive power, which will cause capacitor damage and power factor reduction. Install three phase filter reactors to suppress and absorb harmonics, protect capacitors, avoid the effects of harmonic voltage current and impulse voltage current, improve power quality, increase system power factor, and extend capacitor life
Standard:
● GB/T 1094.6-2011
● GB/T 19212.1-2016
Features
● Designed with secondary thermal sensitive temperature protection switch
● Full vacuum dipping process, low noise during operation
● Winding frame is reinforced environmental protection flame retardant plastic
Model and Meaning
CKSG |
-
|
-
|
-7%
|
P |
K |
│ |
│ |
│ |
│ |
│ |
│ |
1 |
2 |
3 |
4 |
5 |
6 |
No. |
Name |
Meaning |
1 |
Series code |
Dry air-cooled three phase series filter reactor CKDG: single phase |
2 |
Matching Capacitor rated voltage (kV) |
|
3 |
Rated capacity of matched capacitor (kvar) |
|
4 |
Rated reactance rate XL / Xc (%) |
△ :three phase compensation; Y:split phase compensation |
5 |
P: terminal block |
RS485 |
6 |
K: with temperature protection switch |
No mark: without temperature protection switch |
Technical Parameters
Normal working and installation conditions
Ambient temperature |
-25°C~+50°C |
Relative humidity |
Relative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C |
Altitude |
≤ 1000m |
Performance |
|
Rated voltage of capacitor |
0.4 kV、0.45 kV、0.48 kV、0.525 kV、0.66kV、0.69 kV; |
Reactance ratio |
Reactance rate 4.5%, 5%, 6%, 7% is used to limit switching inrush current and suppress 5th and above harmonics
|
Reactance ratio |
Reactance rate 12%, 14%, used to limit closing switching current and suppress 3rd and above harmonics
|
Withstand voltage level 3.5kV / min |
5kV/min |
Insulation class |
B, F, H; Noise ≤ 45dBz continuous operation under overload capacity ≤ 1.35ln |
Dimension and structure |
Product category |
Specification |
Dimension WxDx H(mm) |
Mounting dimensiWxD(mm) |
|
CKSG 7% copper wire |
5~10 kvar |
210x145x170 |
110×85
|
15-25 kvar |
210x155x175 |
110×85
|
30-50 kvar |
240x160x215 |
135×110
|
CKSG 7% Aluminum wire |
5~8 kvar |
210x150x170 |
110×85
|
10-15 kvar
|
210x150x170 |
110×85
|
20-25 kvar
|
240x155x195 |
135×110
|
30-35 kvar
|
240x155x215 |
135×110
|
40-50 kvar
|
262x180x215 |
150×110
|
CKSG 14% copper wire |
25-30 kvar
|
240x160x200 |
135×110
|
CKSG 14% Aluminum wire |
25-30 kvar
|
270x190x215 |
150×120
|
CKSG 14% copper wire. Aluminum wire |
40-50 kvar
|
290x190x240 |
180×120
|
Product detail pictures:
Related Product Guide:
Our goods are commonly recognized and reliable by consumers and may satisfy continually developing economic and social needs for China Wholesale Reactive Power Compensation Pricelist - Three phase series filter reactor – LASTONE , The product will supply to all over the world, such as: Poland, Tanzania, Juventus, Providing the best products, the most perfect service with the most reasonable prices are our principles. We also welcome OEM and ODM orders.Dedicated to strict quality control and thoughtful customer service, we are always available to discuss your requirements and ensure full customer satisfaction. We sincerely welcome friends to come negotiate business and start cooperation.