CJ19 (16) -25, 32, 43, 63, 85, 95 switching capacitor contactors are used to switch low voltage shunt capacitors. They are widely used in reactive power compensation equipment with 380V 50hz. The contactors are equipped with a device to restrain inrush current, which can effectively reduce the impact of closing inrush current on the capacitor and reduce the switching overvoltage at the moment of disconnection.It can replace the original switching device consisting of a contactor and 3 pieces of currentlimiting reactors, which is small in size and light in weight. Strong on-off capacity and easy installation
Standard: GB/T 14048.4-2010
● Normal working conditions and installation conditions
● Ambient temperature: Relative humidity ≤ 50% at 40℃ ;≤ 90% at 20℃
● Altitude ≤ 2000m
● Environmental conditions :No harmful gas and steam,no conductive or explosive dust, no severe mechanical vibration
● The inclination of the mounting surface and the vertical surface is not greater than 5 °
● Pollution degree: Class 3
● Installation Category: Class III
CJ | 19 | - | □ | / | - | □ | / | □ |
| | | | | | | | | | ||||
1 | 2 | 3 | 4 | 5 |
No. | Name | Meaning |
1 | Switching capacitor contactor | CJ |
2 | Design No. | 19(16) |
3 | current (A) | |
4 | Auxiliary contact combinations | |
5 | Operating voltage (coil voltage) | 220V or 380V |
No. | Specification |
25 |
32 |
43 |
63 |
85 |
95 |
Capacity/kvar | 230V |
6 |
9 |
10 |
15 |
20 |
32 |
400V |
<12 |
<16 |
18-20 |
25-30 |
35-40 |
45-50 |
|
Rated insulation voltage (V) |
500 |
500 |
500 |
500 |
500 |
500 | |
Rated working voltage (V) |
380 |
380 |
380 |
380 |
380 |
380 | |
Current (A) |
25 |
32 |
43 |
63 |
85 |
95 | |
AC-6bRated working current(A) |
17 |
26 |
29 |
43 |
58 |
72 |
|
Inrush peak capacitor rated current |
20le |
20le |
20le |
20le |
20le |
20le |
|
Control coil voltage (V) |
220/380 |
220/380 |
220/380 |
220/380 |
220/380 |
220/380 |
|
Coil insulation level |
Class B |
Class B |
Class B |
Class B |
Class B |
Class B |
|
Auxiliary contact current (A) |
6 |
6 |
6 |
10 |
10 |
10 |
|
Operating frequency (times / h) |
120 |
120 |
120 |
120 |
120 |
120 |
|
Electrical life (times) |
105 |
105 |
105 |
105 |
105 |
105 |
|
Mechanical life (times) |
106 |
106 |
106 |
106 |
106 |
106 |
*Note: in addition to screw installation, the contactor can also be installed with a standard clip-in fast-track insertion method. For Cj19-25, 32 and 43 contactors, the width of clamping rail is 35mm, and for Cj19 (b) – 63, 85 and 95 contactors, the width of clamping rail is 35mm or 75mm.